Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY ISSUE OF AUGUST 01, 2007 FBO #2074
SOLICITATION NOTICE

Z -- Construct Transformer Station Building and Replace Medium and Low Voltage System, Building # 327, East Camp Grafenwoehr

Notice Date
7/30/2007
 
Notice Type
Solicitation Notice
 
NAICS
238210 — Electrical Contractors
 
Contracting Office
RCO Bavaria, Attn: AEUCC-G, Unit 28130, APO, AE 09114-8130
 
ZIP Code
09114-8130
 
Solicitation Number
W912PB07B8013
 
Response Due
8/14/2007
 
Archive Date
10/13/2007
 
Small Business Set-Aside
N/A
 
Description
- The project shall be performed within the Training Area Grafenwoehr. - Dismantle the existing medium-voltage and low-voltage installation devices in the old transformer station, Building # 327, consisting of: 1 each existing oil-filled transformer 400 kVA 1 each existing medium-voltage switch system consisting of 5 each medium-voltage cells 1 each existing low-voltage switch system, l x w x d = 4.0 m x 1.0 m x 0.3 m 1 each existing 60 V battery system Dismantle existing medium-voltage cables, low-voltage cables and EMCS cables and/or relocate to the new station. Dismantle all existing metal constructions. - Provide a new transformer building with cable vault and gable roof, roof slope 30 degrees. Dimensions of building: approx. size 8.90 m x 3.0 m, clear height 2.60 m Dimensions of cable vault of reinforced concrete, 0.90 m high - Install a medium-voltage switch system 24 kV consisting of: 2 each 24 kV switch-board sections (transformer section with load disconnector switch) 3 each 24 kV switch-board sections, circuit breaker 1 each 24 kV secured cable switch board section with load disconnector switch as reserve cell 2 each 20 kV oil-filled transformers 630 kVA - Install a low-voltage switch system consisting of: 2 each transformer circuit breakers 1000 A 1 each bus bar system 2000 A 17 each fuse-load-disconnector strips 400 A 9 each fuse-load disconnector strips 160 A 3 each electronical distance protection relays/earth fault directional relays - Install an electrical distribution, a lighting system as well as an electrical heating in the existing Station Building # 327. - Provide 2 access roads for the new transformer station. Asphalt the access roads leading to both front sides.
 
Place of Performance
Address: RCO Bavaria Attn: AEUCC-G, Unit 28130, APO AE
Zip Code: 09114-8130
Country: EU
 
Record
SN01356440-W 20070801/070730221731 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.